AS 1851 counting

How the tester counts toward the year

The app keeps the tally so nobody works it out from last visit's paperwork.

Half

of the smoke detectors on each loop, every year. All of them within two years.

A fifth

of the heat detectors on each loop, every year. All of them within five years.

All

manual call points, flame detectors, beam detectors and any detector that triggers a suppression system, every year.

These are the AS 1851-2012 figures as used in the Magnifire app, counted on each circuit (each loop on an addressable panel).

What counts

  • A device counts when the panel reports an alarm from it during a test.
  • It also counts when the technician marks it passed by hand. Those are labelled in every report.
  • A device marked N/A is left out of the count, and the app asks for a reason.

When a device fails

  • It stays due until it passes.
  • The app asks for 10 more devices on that circuit to be tested.
  • If a second device fails on that circuit, the whole circuit is due.

Two ways to count a site

AS 1851 sample method. The figures above, counted loop by loop.

Every device, every year. For sites where the owner or the contract asks for all devices to be tested annually.

The method is set site by site, in the app or the portal.

The countdown

The number on the technician's screen is how many more devices have to pass for the site to meet the year's target under the method chosen. Failed devices waiting on a repair are shown separately.

The tester keeps the count. It doesn't replace your own reading of the standard or what your contract requires.

Watch the count move

In the demo, fail a device and see the extra 10 appear. Fail a second on the same loop and the whole loop becomes due.